E42-248 · Corrosion Failure · Circulating cooling water pipe · ★★★
After one year, slime fouling on the pipe wall reached 3mm thick and flow dropped 40%.
[Microbe] Anaerobic bacteria grew inside the pipe; slime attached and scaled to 3mm thick. [Blockage / reduced flow] Flow area decreased and flow dropped 40%. [Design Omission] No biocide dosing, low flow velocity, no pigging.
1.Periodically dose oxidizing biocide.
2.Raise flow velocity to 1.5m/s.
3.Provide pipe cleaning openings.
4.Monitor bacterial count in water.
5.Mechanically pig the pipe quarterly.
6.Change pipe material to stainless-steel-lined.
7.Control nutrients in makeup water.
8.Add side-stream filtration.
GB/T 50050-2017