Knowledge Base › Structural Design Error Case Study › Microbial Corrosion of Cooling Tower Fill Support

Microbial Corrosion of Cooling Tower Fill Support

E42-440 · Corrosion Failure · FRP cooling tower support · ★★

Problem Description

FRP cooling tower steel support (humid): microbial corrosion, section thinned 30%, collapse risk; repaired twice a year

Root Cause

[Microbiological corrosion] Oxygen concentration under biofilm, corrosion rate 0.3mm/a. [Thinning] Section steel thins 0.3mm per year, instability. [Design Omission] No biocidal coating, insufficient corrosion protection; safety factor 1.3 (should be ≥2.0).

Corrective Solution

1) Change support to hot-dip galvanized section steel;
2) Add biocidal algaecide;
3) Thicken coating;
4) Measure thickness quarterly;
5) Ventilate and dehumidify;
6) Water treatment;
7) Limit load;
8) Replace at end of life.

Checklist

Reference

GB/T 7190.1-2018