MOULDLKnowledge Base3D Model DownloadsMembership
中文版Model Store »
Knowledge Base › Structural Design Error Cases › Rapid Valve Closure Causes
HomeModels
Table of contents

Knowledge Base Home

📐 Standard Data

🧮 Calculators

📖 Selection Guides

🏭 Material Grades

❓ Engineer FAQ

🗂 Quick-Reference Categories

❌ Error Case Studies

📚 Technical Articles

Rapid Valve Closure Causes Water Hammer and Bursting of the Supply Pipe

E42-132 · Impact & Overload Fracture · Water Supply Pump Station Piping · ★★★

Problem Symptom

Rapid valve closure produces water hammer and the pipe section bursts

Root Cause

[Water Hammer Pressure] The valve closes in 0.5s and the water hammer pressure rise ΔP=ρcΔv reaches a peak of 2.5MPa, above the pipe strength.
[Bursting] The instantaneous overpressure bursts the weld of the pipe section.
[Design Omission] No slow-closing valve or water hammer arrestor was fitted.

Correct Solution

1) Change to a slow-closing check valve to extend the closing time;
2) Install a water hammer arrestor or surge bag;
3) Calculate the water hammer pressure of the piping system;
4) Size the pipe wall for the peak pressure;
5) Limit the valve operating curve;
6) Patrol the piping and measure the wall thickness;
7) Repair-weld and re-inspect the burst section;
8) Include water hammer in the piping design.

Checklist

References

GB 50235 Code for Construction of Industrial Metal Piping Engineering

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL