E42-132 · Impact & Overload Fracture · Water Supply Pump Station Piping · ★★★
Rapid valve closure produces water hammer and the pipe section bursts
[Water Hammer Pressure] The valve closes in 0.5s and the water hammer pressure rise ΔP=ρcΔv reaches a peak of 2.5MPa, above the pipe strength.
[Bursting] The instantaneous overpressure bursts the weld of the pipe section.
[Design Omission] No slow-closing valve or water hammer arrestor was fitted.
1) Change to a slow-closing check valve to extend the closing time;
2) Install a water hammer arrestor or surge bag;
3) Calculate the water hammer pressure of the piping system;
4) Size the pipe wall for the peak pressure;
5) Limit the valve operating curve;
6) Patrol the piping and measure the wall thickness;
7) Repair-weld and re-inspect the burst section;
8) Include water hammer in the piping design.
GB 50235 Code for Construction of Industrial Metal Piping Engineering