Cavitation and vibration noise in a hot water circulation pump handling a high-temperature medium

E44-052 · Pump Selection & Cavitation · Hot Water Circulation Pump · ★★

Problem Symptom

At 95 degrees Celsius the saturation vapour pressure rises and NPSHa drops from the design 4.0m to 2.6m, below NPSHr=3.5m; the pump vibration intensity of 7.1mm/s exceeds 4.5 and the cavitation noise is pronounced

Root Cause

[Cavitation Mechanism] The temperature rise greatly increases pv, so NPSHa=(pa-pv)/rho*g plus the velocity term falls below NPSHr and cavitation occurs with bubble collapse.
[Calculation] At 95 degrees Celsius pv=84.5kPa, which is 82kPa above the 2.3kPa at 20 degrees Celsius, so NPSHa drops by about 2.6m to 2.6m against 3.5m.
[Design Omission] No temperature correction of the cavitation margin was made for the high-temperature medium and no booster priming was provided, so cavitation caused vibration and noise.

Correct Solution

1) Raise the inlet pressure or provide booster priming so that NPSHa is at least 4.0m: at 95 degrees Celsius pv=84.5kPa is 82kPa above the 20 degrees Celsius value, dropping NPSHa by about 2.6m to below 3.5m, so pressurising compensates for the temperature drop;
2) Select the pump using the NPSHr curve corrected for the medium temperature: a high temperature raises NPSHr, so the corrected curve has to be used;
3) Insulate the suction line to limit temperature drop and fluctuation: a stable temperature keeps pv stable and therefore NPSHa stable;
4) Select a pump with a large cavitation margin: a large margin resists the temperature drop;
5) Monitor the inlet pressure and temperature: watching both parameters reveals NPSHa;
6) Define the vibration intensity measuring points on the pump: the 7.1 against 4.5 is a cavitation signature, so vibration has to be measured;
7) Commission the pump and verify the vibration is 4.5mm/s maximum with no cavitation noise: meeting the criteria proves that no cavitation occurs;
8) Include the temperature correction in the selection calculation: the original missing temperature correction was the root cause of the cavitation, so selection must always include it.

Checklist

References

GB/T 13006-2013 Centrifugal Pumps - Efficiency