Flow imbalance between parallel pumps cavitates one pump

E44-208 · Pump Selection & Cavitation · Two Parallel Centrifugal Pumps IS150-125-250 · ★★★

Problem Symptom

In parallel operation the flow of a single pump shifted to 1.3Q against a design 1.0Q, and at that off-design point NPSHr rose to 3.8m against NPSHa of 3.3m, cavitating one pump

Root Cause

[Cavitation] The superposition of the parallel characteristics pushes each individual pump towards high flow, and NPSHr rises at high flow.
[Calculation] NPSHr increases with Q squared, so raising Q from 1.0 to 1.3 lifts NPSHr by about 1.7 times, from 2.8 to 3.8m against NPSHa of 3.3m.
[Design Omission] The NPSHr of a single pump at high flow was not checked for the parallel duty, so cavitation occurred.

Correct Solution

1) Check the actual operating point flow of each pump in parallel operation: the parallel flow is not a simple sum, so this locates the true Q;
2) Take NPSHr at the maximum single-pump flow for the check: NPSHr is high at large Q, so the most severe point is covered;
3) Select a pump with a steep characteristic curve to limit the flow imbalance: a steep curve distributes flow steadily, so the imbalance stays small;
4) Keep the parallel pumps identical in model and size: mismatched pumps tend to maldistribute, so the balance is maintained;
5) Fit a balancing valve on each pump discharge to trim the flow: this allows active equalisation, so no single pump is overloaded;
6) Enlarge the common suction header: a large Q demands a low velocity, so NPSHa is sufficient;
7) Commission the parallel duty and measure the flow and inlet pressure of each pump: the design requirement must be verified by measurement, so this confirms the delivery;
8) Include the parallel duty check in the selection: checking only the single pump was the root cause, so the design must always include it.

Checklist

References

GB/T 13006-2013 Centrifugal Pumps - NPSH