E44-056 · Excessive Piping Resistance & Pressure Drop · Pipe run with many elbows and a valve group · ★★
Twelve elbows and six valves accumulated local losses, so hj=Σζv²/2g=4.2m against a design value of 2.5m; the system pressure drop is large and the pump easily overloads
[Local Loss] hj=Σζ·v²/2g, and the ζ values of the elbows and valves stack up.
[Calculation] Σζ=12×0.3+6×2.0=15.6, v=2.3m/s, so hj=15.6×0.27≈4.2m against the design value of 2.5m.
[Design Omission] The layout was not optimised to reduce elbows and valves and the local losses were not counted, so the pressure drop is large.
1) Optimise the pipe routing to reduce the number of elbows (from 12 to ≤6), because each 90° elbow has ζ≈0.3 and removing one saves about 0.08m of loss, so Σζ falls and the system pressure drop returns to near the design value;
2) Change to large-radius bends (R≥1.5D) to reduce ζ, because the local resistance coefficient of a large-radius elbow falls from 0.3 to 0.2, thereby further reducing the local loss with the same layout;
3) Group the valves together and reduce the throttling branches, because dispersed valves each carry their own local loss whereas grouped valves can share the straight runs for conditioning, so Σζ falls and operation is easier;
4) Provide a bypass to reduce the throttling loss, because a regulating valve throttles continuously at a high ζ and the bypass shares flow to lower the main line velocity, thereby reducing the total pressure drop at part load and preventing pump overload;
5) Check the total local loss and issue a calculation sheet, because simply counting elbows easily omits the valve ζ (2.0 each), so that hj is computed precisely as Σζ·v²/2g;
6) Install pressure measurement points along the line, because the local losses are concentrated in the valve group and the high-drop section must be located, thereby guiding the subsequent targeted rectification;
7) Measure the total system pressure drop and the pump current during commissioning, because a large drop directly overloads the pump and pushes the current above rating, thereby confirming that the modification prevents overload;
8) Make the local losses a mandatory item in the hydraulic calculation sheet, because omitting them is the main reason the pressure drop exceeded the limit, thereby calculating them fully and leaving margin at the design stage.
GB/T 20801-2020 Pressure Piping Code