E44-158 · Excessive Piping Resistance & Pressure Drop · DN80 supply pipe (should be DN100) · ★★
Selecting DN80 gave v=3.1m/s, and since the resistance follows v² it became 2.4 times the design value, overloading the pump
[Small Diameter] The small pipe diameter raises v.
[Quadratic Loss Law] hf∝v² rises 2.4 times.
[Design Omission] The diameter was not selected on the design velocity, so the resistance is large.
1) Select the pipe diameter for the design velocity (1.5 to 2.5m/s for liquids), because DN80 giving v=3.1m/s makes the resistance 2.4 times the design value, thereby selecting a diameter that reduces the resistance;
2) Recalculate the friction loss with hf∝v² and re-check the pump, because the quadratic term has increased, thereby recalculating and selecting the pump accordingly;
3) Upgrade the pipe to DN100 to lower v, because the small diameter raised v, thereby increasing the diameter;
4) Check that the pump is not overloaded, because the high resistance pushes the flow and the power up, thereby checking the power;
5) Install a velocity monitor with an alarm, because an excessive velocity gives a high resistance, thereby monitoring the velocity;
6) Measure the resistance and flow during commissioning to confirm compliance, because the design requirement must be verified by measurement, thereby closing out the acceptance;
7) Leave cleaning allowance in the network so that scale does not raise the resistance, because scale increases the resistance, thereby keeping the margin;
8) Incorporate pipe diameter optimisation into the design, because the original small diameter was the root cause of the high resistance, so the design must include it.
GB/T 20801-2020 Pressure Piping Code