E44-050 · Other · Crude-Oil Storage-Tank Breather Valve · ★★
A frosted breather valve pulled a vacuum inside the tank during filling/emptying; the roof buckled inward 0.4m deep.
[Blocked] The valve disc froze shut, leaving the venting area at zero; filling and emptying then generated ±pressure.
[Collapse] The negative pressure buckled the roof.
[Design Omission] No heat tracing or insulation, and no standby valve; blockage led to collapse.
1) Heat-trace and insulate the breather valve against frost; a frozen disc leaves zero vent area, filling/emptying generates ±pressure, and the roof collapses, so insulate against freezing;
2) Install two valves, one duty and one standby; if one blocks the other vents and breathing is not interrupted, so use twin valves;
3) Exercise the valve disc periodically to prevent sticking; movement prevents seizing, so exercise it;
4) Check the roof for external-pressure stability; negative pressure buckles the roof, so check external pressure;
5) Provide an emergency venting manway; emergency pressure relief protects the tank, so add the manway;
6) Size the venting capacity for the maximum fill/empty rate; insufficient venting builds pressure, so check the capacity;
7) Verify free breathing on commissioning; free flow proves it, so verify it;
8) Bring freeze protection and venting into tank design; the original lack of insulation was the root cause of collapse, so the design must include it.
GB/T 50322-2019 Storage tank design code