E44-097 · Other · Nitrogen-Blanket Buffer Tank · ★★★
The blanketing valve failed and pulled a vacuum in the tank; it buckled under external pressure, 0.3m deep.
[Negative Pressure] Blanket failure pulls a vacuum in the tank, and external pressure buckles it.
[Calculation] The negative pressure makes Pcr < the operating vacuum, causing buckling and collapse.
[Design Omission] No standby blanketing supply and no external-pressure check; collapse resulted.
1) Provide duty/standby redundancy for the blanketing valve; a single-valve failure leaves no makeup and external-pressure buckling collapses the tank, so the standby valve starts automatically and holds a slight positive pressure to prevent collapse;
2) Check the roof for external-pressure stability per GB/T 150 (Pcr≥1.1× operating vacuum); the buckling critical pressure of a thin shell depends on D0/δ, so wall thickness and stiffening rings get a quantified basis against buckling;
3) Interlock an emergency makeup valve with the blanket; when the nitrogen source fails, pressure must be restored quickly, so short-term tank pressure is held without vacuum;
4) Coordinate the breather valve and blanket setpoints; the breather relief value must sit above the blanket pressure, so positive pressure does not vent nitrogen and negative pressure does not suck in air;
5) Control fabrication roundness ≤1%D0; large ovality concentrates local stress and lowers Pcr, so meeting roundness raises external-pressure resistance;
6) After installation, pull a vacuum test to -0.005MPa and hold; the design calculation needs measured confirmation, so evidence exists before delivery against collapse;
7) Fit a vacuum relief valve on the roof opening at -0.002MPa; an accidental vacuum draws in air to balance, eliminating external-pressure buckling;
8) Bring blanketing and standby logic into the tank design specification; variable duty must be fixed, so reuse later without dropping items.
GB/T 150.3-2011 Pressure vessels - Design