E44-326 · Excessive Piping Resistance and Pressure Drop · Pressure Dropping 0.6→0.2MPa Raising v · ★★
After reduction the density dropped, v rose from 1.5 to 2.8m/s, downstream hf tripled, and end-of-line supply pressure fell short.
[Raised v] Reduction raises specific volume; v=Q/A rises, and hf∝v² triples.
[Shortage] The raised downstream hf lowers the end pressure.
[Design Omission] The post-reduction pipe diameter was not enlarged and specific volume was not checked; resistance after reduction was high.
1) Enlarge the post-reduction pipe so v≤1.8m/s; the pressure drop made v=2.8, tripled hf, and lowered the end pressure, so upsizing controls v;
2) Check v and hf for the post-reduction specific volume; an unchecked specific-volume change caused the loss, so compute accurately;
3) Check total downstream hf with margin; raised v accumulates loss, so leave margin;
4) Choose a low-pressure-loss regulator; valve loss adds to the system, so use a low-loss valve;
5) Add pump head to make up downstream pressure; the end needs pressure, so add head;
6) Monitor flow velocity; raised v is hard to notice, so monitor v;
7) Reduce pressure in stages to stabilize specific volume; a single large step swings the specific volume, so stage it;
8) Record post-reduction hydraulics in the design; the original failure to check was the root cause of resistance, so the design must gate it.
GB/T 20801.3-2020 Design code for industrial metallic piping