E44-199 · Other · System Safety Valve · ★★★
Calibration overdue; the popping pressure was off by 10%, and the valve failed to open on overpressure.
[Uncalibrated] Spring fatigue shifts the popping pressure.
[Failure to Open] The shift leaves it closed under overpressure.
[Design Omission] No scheduled calibration and no lead seal; a hazard remained.
1) Calibrate and set the safety valve on schedule; overdue calibration leaves popping 10% off and it fails to open on overpressure, so calibrate on schedule;
2) Lead-seal the valve after calibration to prevent tampering; any adjustment shifts it, so lead-seal it;
3) Choose the set pressure with suitable redundancy; a single point can drift, so select accurately;
4) Add overpressure alarm to back up safety; the valve can fail, so alarm it;
5) Periodically seat-lift to prevent sticking; a stuck plug jams, so lift the seat;
6) Keep calibration records traceable; analysis needs them, so record them;
7) Verify popping pressure accuracy on commissioning; design requirements need measured confirmation, so confirm at delivery;
8) Bring periodic calibration into safety-management procedures; the original lack of calibration was the root cause of inaccurate popping, so the procedure must include it.
GB/T 12241-2005 Safety valves - General requirements