E44-201 · Other · Steam Trap · ★★
Wrong selection (a continuous-leak type) vented live steam directly, wasting energy and consuming 20% more steam per month.
[Wrong Type] Wrong selection vents steam straight through.
[Energy Waste] Direct venting wastes steam.
[Design Omission] Not selected by duty and not tested; energy was wasted.
1) Select the correct trap type by duty (float / thermostatic / bimetallic); a wrong type vents steam directly and wastes 20% more per month, so choose the right type;
2) Size capacity by condensate discharge; too small leaks steam and too large plugs, so fit the capacity;
3) Run a trap-efficiency test; steam leakage wastes energy, so measure efficiency;
4) Fit a downstream sight glass to prevent direct venting; direct venting is hard to notice, so watch it;
5) Periodically check operation against leakage; it leaks gradually, so check periodically;
6) Insulate to cut flash loss; radiation wastes energy, so insulate;
7) Verify no steam loss and energy target on commissioning; design requirements need measured confirmation, so confirm at delivery;
8) Bring selection into drain design; the original wrong type was the root cause of steam loss, so the design must include it.
GB/T 12247-2015 Steam traps - Classification