E44-1097 · Other · Spray Pipe · ★★
Biased, distribution, uneven.
[Mechanism] Hole distribution in the spray pipe was uneven and supply pressure fluctuated; local dry-out on the heat-transfer surface caused scaling.
[Calculation] Pipe 6m long, hole spacing off by ±15mm; end pressure 0.15MPa, 40% below the 0.25MPa at the start; water-distribution uniformity 70%.
[Design Omission] No distribution-uniformity check, no pressure stabilization, no hole-spacing check, and no distribution test.
1) Check water-distribution evenness (equal hole spacing ±3mm); bias causes unevenness, and even spacing evens the spray;
2) Control pressure steadily (0.25±0.02MPa); low pressure causes bias, and stable pressure evens water distribution;
3) Check hole spacing (tapered holes to compensate pressure drop); bias causes unevenness, and checked spacing evens distribution;
4) Add flow-guiding plates (even flow against turbulence); turbulence biases, and guiding stabilizes even distribution;
5) Run a distribution test (uniformity ≥90%); untested means unknown, and measured evenness confirms it;
6) Install flow monitoring (alarm on bias); bias first shows as a flow difference, and early warning catches it;
7) Level the supports (levelness ≤2mm/m); tilt causes bias, and leveling evens the spray;
8) Record distribution and spacing on the spray drawing; the root cause of bias was uneven hole spacing and pressure fluctuation, so the drawing must gate it.
GB/T 50050-2017 Industrial circulating cooling water