E44-1105 · Other · Temporary Pipe · ★★
Vibration, loosening, noise.
[Mechanism] The temporary pipe had insufficient supports and high velocity; the von Kármán vortex excitation frequency neared the pipe natural frequency, causing resonant loosening.
[Calculation] Pipe DN80, velocity 6m/s; St=0.2; f=St·v/d=0.2×6/0.08=15Hz, near natural f_n=16Hz; amplitude 0.8mm.
[Design Omission] No added supports, no span check, no velocity control, and no vibration test.
1) Add supports (spacing ≤3m); looseness vibrates, and support stabilizes it, damping vibration;
2) Control velocity ≤3m/s (slow down); high velocity vibrates, and lower velocity stabilizes it, suppressing vibration;
3) Check span (≤3m against sag); a large span vibrates, and a small spacing fixes the pipe, stabilizing it;
4) Add a damper (absorb vibration); vibration causes noise, and damping absorbs it, cutting amplitude;
5) Run a vibration test (amplitude ≤0.15mm); untested means unknown, and measured stability confirms it;
6) Install vibration monitoring (alarm on over-limit); vibration first shows as amplitude, and early warning catches it;
7) Time-limit use (remove within 3 months); long service loosens, and a time limit replaces it, preventing loosening in service;
8) Record support and span check on the temporary-pipe drawing; the root cause of vibration was no support and high velocity, so the drawing must gate it.
GB/T 20801.3-2020 Industrial piping