E44-1107 · Other · Freeze Protection · ★★
Missing, frozen, cracked.
[Mechanism] Freeze-protection heat tracing was off and insulation was missing; the low-temperature line medium froze and expanded, cracking the pipe.
[Calculation] Ambient −15℃, water 4℃; without tracing the pipe fell to −5℃; water froze and expanded 9%, internal pressure rose to 10MPa>allowable, and cracked.
[Design Omission] No heat tracing, no insulation, no power check, and no freezing test.
1) Provide electric heat tracing (25W/m, constant 40℃); missing tracing freezes, and heat tracing melts it, preventing freeze-cracking;
2) Add insulation (δ=40mm); radiation freezes, and insulation protects, suppressing freezing;
3) Check sufficient power (by heat loss); low power freezes, and adequate power holds temperature, keeping heat;
4) Control temperature startup (auto-start <5℃); low temperature freezes, and temperature control protects, preventing freezing;
5) Run a freezing test (−20℃ held 24h without cracking); untested means unknown, and measured toughness confirms it;
6) Install temperature monitoring (alarm <5℃); freezing first shows as a temperature drop, and early warning catches it;
7) Set an inspection interval (before winter); long intervals leave it missing, and controlled intervals inspect, preventing freezing in service;
8) Record protection and insulation on the freeze-protection drawing; the root cause of cracking was no tracing and no insulation, so the drawing must gate it.
GB/T 4272-2008 Thermal insulation for equipment and pipelines