E44-1109 · Other · Cleaning System · ★★
Low pressure, rinse, not clean.
[Mechanism] The cleaning pump head was insufficient and the line had a blockage; jet pressure fell below the cleaning threshold, leaving scale unclean.
[Calculation] Required 0.6MPa, actual 0.35MPa; nozzle outlet velocity v=√(2ΔP/ρ)=√(2×0.35e6/1000)=26m/s (should be ≥35); scale-removal rate 60%.
[Design Omission] No pump-pressure check, no blockage hunt, no bore check, and no cleaning test.
1) Check pump pressure ≥0.6MPa (replace with a higher-head pump); insufficiency leaves it unclean, and adequate pressure cleans it;
2) Hunt blockage points (measure pressure section by section); a blockage leaves pressure short, and finding it restores pressure;
3) Check bore DN50 (replacing DN32 to cut resistance); a small bore leaves pressure short, and an adequate bore flows, holding pressure;
4) Stabilize flow (constant-pressure supply); low pressure leaves it unclean, and steady flow cleans it evenly;
5) Run a cleaning test (scale-removal ≥90%); untested means unknown, and measured cleanliness confirms it;
6) Install pressure monitoring (alarm on low pressure); insufficiency first shows as a pressure drop, and early warning catches it;
7) Set a calibration interval (monthly); long service leaves pressure short, and controlled intervals calibrate, preventing drop in service;
8) Record pump pressure and blockage hunt on the cleaning drawing; the root cause of insufficiency was low pump head and a blockage, so the drawing must gate it.
GB/T 50050-2017 Industrial circulating cooling water