E44-331 · Excessive Piping Resistance and Pressure Drop · A swing check valve used in frequent-flow service · ★★
A swing check valve with ζ=2.5 far exceeds the butterfly type's 0.3; the whole system drops an extra 0.06MPa and pump power use rises by 10%
[Mechanism] The swing check has ζ=2.5, far higher than the butterfly type, and its losses stack up.
[Calculation] The extra 0.06MPa pressure drop raises power use by 10%.
[Design Omission] No low-resistance check valve chosen to suit the flow regime and no loss check - the check resistance stayed high.
1) Switch to a low-resistance butterfly or dual-plate check valve (ζ≤0.5), since the swing valve's ζ=2.5 adds 0.06 loss and 10% power, giving low resistance;
2) Include the check valve's local loss in the total hf, since omitting it undercounts the stacked loss, giving a complete account;
3) Favor low-resistance types for large diameters, since loss is more pronounced on large lines, choosing the low-resistance type;
4) Locate it in a straight, low-loss run, since losses stack worse in high-loss sections, placing it low-loss;
5) Add a bypass to cut throttling, since the check valve constantly throttles, giving a bypass;
6) Size the selection by flow velocity, since loss rises with v, sizing by v;
7) Periodically check that the disc moves freely, since sticking raises loss, inspecting the disc;
8) Write check-valve loss into the design, since the missing loss check was the root cause, closing the loop at design.
GB/T 20801.3-2020 Design code for industrial metallic piping