E44-1025 · Excessive Piping Resistance & Pressure Drop · Valve · ★★
High valve resistance, pressure drop, sluggish control
[Mechanism] The selected valve has a large local resistance coefficient (a globe valve has xi=6~8), so more than half of the system pressure drop is spent on the valve and the control response is sluggish.
[Calculation] The original DN150 globe valve with xi=7 at v=2.0m/s gives hf_valve=7x2.0^2/19.6=1.43m, 38% of the total resistance, with a long control travel and a slow response.
[Design Omission] A low-resistance valve was not selected, xi was never verified, and no selection comparison was made.
1) Change to a low-resistance gate valve or butterfly valve (xi falls from 7 to 0.3); the original globe valve at xi=7 gave hf_valve=1.43m, 38% of the total resistance, so changing the valve lowers the resistance and the system pressure drop falls by 1.1m;
2) Verify the valve xi at <=0.5 (using the manufacturer resistance curves); a large xi causes the pressure drop and the check quantifies it;
3) Run fully open with control margin retained (valve opening 70%~100%); operating at half open makes xi jump, while fully open lowers it, reducing the resistance;
4) Enlarge the valve to DN200 (equal to the pipe diameter so v falls); a reduced diameter raises xi and equal sizing slows it, reducing the resistance;
5) Carry out a valve resistance test (measure the DeltaP-Q curve); without the test the real xi is unknown, so measurement validates it and the data fixes the resistance;
6) Raise the pump head with a 10% margin; a high valve resistance leaves the terminal under-pressurised and raising the head compensates, securing the flow;
7) Control the flow at or below design (above that v^2 raises the resistance); excess raises hf and controlling it slows the rise, keeping the resistance steady in operation;
8) Write the valve selection and the xi verification into the specification; the root cause of the high valve resistance was a missing low-resistance valve selection with no verification, so the specification closes the loop.
GB/T 20801.3-2020 Design Code for Industrial Metallic Piping