E44-267 · Valve Selection and Internal Leakage · Lift check valve H41H-16 DN80 · ★★
On pump shutdown the closure impact is 105dB, the disc rebounds 15mm, and adjacent piping vibration severity is 4.5mm/s
[Mechanism] The disc free-falls to seat at v=√(2gH), and its kinetic energy ½mv² slams into the seat.
[Calculation] Sudden trip produces a shock wave Δp=ρcΔv=0.8MPa.
[Design Omission] No slow-closing or damping and no water-hammer calculation - the check slammed shut.
1) Switch to a slow-closing check to extend re-seating to 3-5s, since the free-fall v=√(2gH) rebounded 15mm at 105dB, cushioning to cut impact;
2) Add a rubber bumper to the disc to absorb energy, since the hard impact was loud, damping vibration and noise;
3) Fit a water-hammer arrestor to absorb the Δp=0.8MPa wave, since the wave drove vibration to 4.5mm/s (over limit), trimming the peak;
4) Add a VFD soft-stop at the pump outlet, since sudden trip is the wave source, easing the stop to cut the wave;
5) Fit fixed supports and hangers to resist vibration, since impact transmits vibration, anchoring the piping;
6) Check closing speed at selection to control Δv, since Δp∝Δv and fast closing raises pressure, closing slowly;
7) Periodically inspect the disc and bumper parts, since aging kills the cushion, replacing early;
8) Put water-hammer calculation into the design, since the missing calc was the impact-noise root cause, closing the loop at design.
GB/T 12233-2006 General purpose valves - Iron globe valves and lift check valves