E44-269 · Valve Selection and Internal Leakage · Three-way control valve T-type DN80 · ★★
Reversed installation made the two media mix at a 1:1 ratio and cross-contaminate; 5% of batches were rejected and rework ran 2t/day.
[Flow Direction] The internal flow passage is designed for one direction; reversing it flips the split ratio and lets the two lines interconnect.
[Cross-Flow] Even in the shut-off position an internal leak path remained, causing cross-contamination.
[Design Omission] No flow-direction arrow was marked and no flow-direction test was run — the three-way valve cross-leaked.
1) Reinstall in the correct direction per the body arrow; reversing flipped the split ratio and mixed the two lines 1:1 with cross-contamination and 5% rejection, so align the flow;
2) Mark a prominent flow arrow on the body and keep a photo on file; without marking it was easy to reverse, so make it visible;
3) Run flow-direction and shut-off tests to check internal leakage; the shut position still cross-leaked, so verify the seal;
4) Add independent shut-off valves at critical points as a backup; cross-flow ruins quality, so provide isolation;
5) When media mutually contaminate, switch to double-valve isolation; a single valve cannot fully cut off, so seal it tight;
6) During commissioning, measure both line concentrations to confirm no cross-flow; cross-contamination is invisible to the eye, so quantify it;
7) Prepare an installation flow-direction card; the lack of marking was the root cause of the reversal, so install to the card;
8) Add a flow-direction check to commissioning; the missing step caused the cross-flow, so gate it during commissioning.
GB/T 17213.1-2015 Industrial-process control valves