E44-271 · Valve Selection and Internal Leakage · Motorized gate valve MZ941H-16 DN150 · ★★★
A failed torque switch let over-torque reach 2.5× the rated value; the stem bent and fractured, and the wedge stuck half-open.
[Failure] The torque sensor drifted so the protection never tripped and force kept rising.
[Stem Break] The stem stress exceeded yield σ_s and it bent and fractured.
[Design Omission] The torque switch was never calibrated and no dual travel protection was provided — the motorized valve's stem broke.
1) Calibrate the torque switch so the trip point = 1.1× rated; the drift let over-torque reach 2.5× and bent the stem, so limit the force;
2) Make travel and torque protection back each other up; if torque protection fails, travel still trips — a double safeguard;
3) Design the stem strength to a 2× safety factor; overload breaks it easily, so make it thicker;
4) Periodically calibrate the torque sensor; drift is gradual, so recalibrate on schedule;
5) Add over-current protection to stop the motor; when torque protection fails the current still runs high, so cut power to end the hazard;
6) Provide a manual bypass for emergency open/close; after the stem breaks the valve is dead, so keep manual operation;
7) During commissioning, measure the full-travel torque curve; abnormal torque signals jamming, so diagnose early;
8) Include torque and travel verification in the procedures; the lack of calibration was the root cause, so gate it in O&M.
GB/T 28270-2012 Intelligent valve electric actuators