E44-277 · Valve Selection and Internal Leakage · Self-operated pressure control valve ZZY-16 DN50 · ★★
A blocked impulse line made control inaccurate: outlet pressure drifted to 0.7MPa (setpoint 0.4), overpressurizing the downstream side.
[Blockage] Fouling or freezing of the impulse line lost the pressure signal, and the diaphragm would not move.
[Drift] With the signal lost, the spring pushed from one side only, drifting the setpoint high.
[Design Omission] No impulse-line flushing or heat tracing and no insulation — the self-operated valve lost accuracy.
1) Add a flush port on the impulse line and blow it through on schedule; fouling/freezing lost the signal and drifted pressure to 0.7MPa, so keep sensing open;
2) Add heat tracing at low temperature against freezing; freezing blocks it the same way, so insulate;
3) Route the impulse line sloping downward to help drain; horizontal runs trap debris, so slope it;
4) Add a gauge for cross-check calibration; inaccuracy is hard to notice, so cross-check;
5) Vent the diaphragm chamber against gas binding; gas binding slows the movement, so vent it;
6) Fit a safety valve on the critical downstream side; the drift caused overpressure, so add backup;
7) Periodically disassemble and clean the impulse system; blockage is gradual, so clear it;
8) Include impulse-line maintenance in the procedures; the missing provision was the cause of inaccuracy, so gate it in O&M.
GB/T 12244-2006 Pressure reducing valves - General requirements