E44-289 · Valve Selection and Internal Leakage · Wafer butterfly valve D71X-10 DN200 · ★★
Pipe thermal-expansion thrust bent the body flange face and cracked the body, which seeped; support settlement added extra stress.
[Stress] Pipe thermal expansion ΔL=αLΔT thrusts the valve beyond the casing allowable.
[Crack] The bending moment cracks the thin-walled body.
[Design Omission] No expansion joint or supports, and no pipe stress calculated — the butterfly valve cracked.
1) Fit an expansion joint in the piping to absorb ΔL=αLΔT thermal expansion; thermal thrust bent and cracked the body, which seeped, so relieve the stress;
2) Place supports on both sides of the valve to carry pipe weight and expansion; settlement adds bending, so anchor the pipe;
3) Size the body strength to the piping thrust; the thin wall cracks easily, so thicken it;
4) Switch to a double-flanged valve to cut installation stress; wafer types skew and bend easily, so mount it stably;
5) Run a piping stress (flexibility) analysis; not calculating it was the cause of cracking, so analyze;
6) Periodically inspect the body for cracks; cracks grow, so diagnose early;
7) Retorque the flanges when hot; thermal expansion displaces them, so retighten;
8) Bring piping stress into the design; the missing provision was the cause of cracking, so gate it at design.
GB/T 12238-2008 Flanged and wafer-resilient-seated butterfly valves