E44-1037 · Valve Selection & Internal Leakage · Valve · ★★
Reverse installation, leakage, backflow
[Mechanism] A check valve or globe valve was installed in the wrong direction, so the medium flows backwards or the globe valve cannot close tightly and leaks in reverse.
[Calculation] DN150 check valve installed backwards, with a forward-flow resistance of xi=2.5 (0.5 or less is required), the disc cannot seat in reverse and 30m3/h flowed backwards.
[Design Omission] The flow direction was never checked, no arrow was marked, and no direction inspection was performed.
1) Reinstall according to the flow direction (the body arrow aligned with the medium); the original reverse installation leaked and correct installation stops the backflow;
2) Mark the flow direction arrow (with conspicuous paint); blind installation causes reversal and marking the flow makes it clear, keeping the direction controllable;
3) Change to a valve that is already correctly installed (confirm the disc seats); reverse installation leaks and correct orientation seats it, sealing the valve;
4) Carry out a flow-direction test (flow forward, blocked in reverse); the leak was never verified and measurement confirms the direction, so the data fixes the orientation;
5) Fit a flow meter downstream of the check valve (monitor a reverse flow of zero); backflow shows up first as reverse flow and early detection gives warning, monitoring the direction;
6) Perform a direction review (label every valve with its tag number); mixed-up valves get reversed and the review confirms it, preventing misinstallation;
7) Keep the upstream pressure above the downstream pressure in operation (to prevent backflow); a reversed pressure difference causes backflow and controlling the difference stops it, preventing backflow in operation;
8) Write the direction verification and flow marking into the assembly card; the root cause of the reverse installation was a missing flow-direction check with no marking, so the assembly card closes the loop.
GB/T 12224-2015 Steel Valves - General Requirements