E44-1038 · Valve Selection & Internal Leakage · Motorised Valve · ★★
Travel error, not reaching position, leakage
[Mechanism] The travel limits of the electric actuator were not set accurately, so the disc did not reach the fully open or fully closed position, producing internal leakage or throttling.
[Calculation] DN200 motorised gate valve with the limit off by 15%; the disc stood 8mm off its seat, internal leakage was 120mL/min, and the actual opening of 85% was wrongly displayed as 100%.
[Design Omission] The travel was never verified, the opening was never calibrated, and no full-open/full-close test was performed.
1) Re-adjust the travel limits (disc fully seated when closed, fully in position when open); the travel error caused the leak and correcting the travel seats the disc, stopping the leakage;
2) Calibrate the opening feedback (4mA fully closed, 20mA fully open); an uncalibrated travel displays wrongly and calibrating makes the reading correct, so the opening indication is trustworthy;
3) Adjust the torque and the limit switches (over-travel torque protection on closing); a mismatch leaks and adjusting the limits closes it, sealing the valve;
4) Carry out a full-open/full-close test (measured opening equals the command); the leak was never verified and measurement confirms the position, so the data fixes the position;
5) Fit a valve position indicator (mechanical and electrical dual indication); an offset shows up first as a position difference and early detection gives warning, monitoring the position;
6) Perform a travel re-check (once per season); over time it drifts and re-checking corrects it, preventing drift;
7) Keep the control signal stable in operation (to prevent interference-driven misoperation); disturbance causes drift and a stable signal keeps it steady, preventing errors in operation;
8) Write the travel verification and the feedback calibration into the specification; the root cause of the travel error was a missing limit adjustment with no calibration, so the specification closes the loop.
GB/T 12224-2015 Steel Valves - General Requirements