E44-115 · Water Hammer and Pressure Surge · Feed-Pump Discharge Piping · ★★★
An abrupt pump trip produces a water-hammer peak of 2.4MPa (pipe rating 1.6MPa); the check-valve disc is shattered and the piping vibrates violently.
[Water Hammer] A sudden pump trip drops the flow velocity to zero and the pressure wave reflects.
[Calculation] Δp=ρcΔv; with c=1000m/s and Δv=2m/s, Δp=2.0MPa, exceeding the pipe rating.
[Design Omission] No slow-closing valve was provided and no water-hammer analysis was done — the valve was shattered.
1) Install a slow-closing check valve at the discharge with closure time ≥2L/c: slow closure keeps Δv small and reduces Δp=ρcΔv, so the peak pressure stays within the rating;
2) Perform a water-hammer analysis to size the protection: the peak pressure must be quantified, giving a basis for selection;
3) Raise the pipe pressure rating to 2.5MPa: the original 1.6MPa was insufficient, so the higher rating resists the peak;
4) Install a water-hammer relief valve (opens on overpressure): it discharges at overpressure, protecting the piping;
5) Use soft pump stop (VFD deceleration): an abrupt stop generates a large Δv, so a gradual stop reduces the hammer;
6) Install pressure monitoring points along the line to track the peak pressure: knowing the distribution allows verification;
7) Run a commissioning test to measure the maximum pressure ≤1.6MPa: the design requirement must be verified on site, confirming delivery;
8) Build water-hammer protection into the piping design: the lack of protection was the main cause, so it must be institutionalized to prevent recurrence.
GB/T 20801.3-2020 Pressure piping code - Industrial piping - Design