E44-117 · Water Hammer and Pressure Surge · Siphon Discharge Pipe · ★★
After pump trip, the pressure at the pipe crown drops to a vacuum and the water column separates; when the cavity collapses it generates a 1.8MPa water hammer, rupturing the pipe.
[Column Separation] The vacuum at the pipe crown pulls the water column apart.
[Calculation] When P<Pv, vaporization and separation occur; on collapse, the Δp=ρcΔv impact ruptures the pipe.
[Design Omission] No venting or make-up water line was provided — the pipe ruptured.
1) Install air valves at the crown to vent accumulated gas: this prevents water-column separation and thus the collapse impact;
2) Provide priming-loss protection that trips the pump and admits make-up water: preventing vacuum separation keeps the pipe full;
3) Reinforce elbow welds and inspect them by NDT: impacts cause cracking, so this ensures safety;
4) Slow-fill start-up to reduce reverse flow: gradual filling keeps Δv small, suppressing the hammer;
5) Install pressure monitoring points along the line to track vacuum: detecting separation early allows prompt action;
6) Install a vacuum breaker at the inlet: it admits air under vacuum, preventing separation;
7) Run a commissioning test to verify there is no cavity reverse flow: the design requirement must be verified on site;
8) Build priming-loss protection into the siphon design: lack of protection was the main cause, institutionalizing prevention.
GB/T 20801.3-2020 Pressure piping code - Industrial piping - Design