E44-165 · Water Hammer and Pressure Surge · Long-Distance Transfer Pump · ★★★
An abrupt pump trip lets the water-column inertia generate a water hammer Δp=ρcΔv=1.2MPa, rupturing the pipe.
[Water Hammer] On pump stop the velocity drops abruptly, generating Δp=ρcΔv.
[Pipe Rupture] Δp=1.2MPa exceeds the pipe pressure rating.
[Design Omission] No slow-closing valve or surge tank was provided — the pipe ruptured.
1) Install a slow-closing check valve at the pump discharge to extend closure: an abrupt trip generated Δp=1.2MPa and ruptured the pipe; slow closure cuts the peak;
2) Install a surge tank to absorb the impact: the hammer overpressures the line, so the tank absorbs and cuts the peak;
3) Use soft pump stop with gradual deceleration: a hard stop changes velocity abruptly, so soft stop changes it gradually;
4) Check the pipe wall thickness against water-hammer pressure: the original design did not calculate the overpressure, so wall thickness is selected by pressure check;
5) Install vents at high points to prevent water-column separation: a collapsed gas column raises pressure, so venting is needed;
6) Provide an overpressure relief valve as a backstop: the peak is hard to predict, so it vents pressure;
7) Run a commissioning test to measure the water-hammer peak ≤ pipe rating: the design requirement must be verified on site;
8) Build water-hammer protection into the pump-station design: the original omission was the root cause of the rupture, so it is mandatory.
GB/T 20801-2020 Pressure piping code