E44-166 · Water Hammer and Pressure Surge · Pump Discharge Check Valve · ★★
A conventional swing check valve closes fast, and the resulting 0.8MPa water-hammer pressure rise leaks at the pump-body flange.
[Fast Closure] The disc drops quickly, cutting the flow and generating hammer.
[Pressure Rise] Δp=ρcΔv=0.8MPa, exceeding the limit.
[Design Omission] A slow-closing type was not selected and closure time was not calculated — pressure rise resulted.
1) Switch to a slow-closing check valve to control closure time: fast closure generated a 0.8MPa hammer and leakage; slow closure cuts the peak;
2) Calculate the closure-time vs. Δp relationship: a short t gives a large hammer, so t is calculated for selection;
3) Install a surge tank downstream of the valve to absorb the peak: the peak exceeds the limit, so the tank absorbs it;
4) Provide soft start and soft stop for the pump: abrupt starts and stops change conditions sharply, so soft transitions are used;
5) Check the flange bolting against the pressure rise: overpressure caused leakage, so bolts are checked;
6) Provide a relief valve as a backstop: the peak is hard to predict, so it vents;
7) Run a commissioning test to measure closure hammer ≤ limit: the design requirement must be verified on site;
8) Include closure characteristics in check-valve selection: the original fast closure was the root cause of the pressure rise, so it is mandatory.
GB/T 20801-2020 Pressure piping code