E44-354 · Water Hammer and Pressure Surge · Motorized Gate Valve 6s Fast Closure · ★★★
Full closure in only 6s produces Δv=2.5m/s, Δp=ρcΔv=1.5MPa, exceeding the pipe rating of 1.0 and cracking the elbow weld.
[Fast Closure] A closure time T<2L/c produces instantaneous water hammer with maximum Δp.
[Overpressure] Δp=1.5 exceeds 1.0, causing cracking.
[Design Omission] Closure time ≥2L/c was not controlled and no slow closing was provided — fast-closure hammer resulted.
1) Tune the closure time to ≥2L/c (e.g., ≥30s): 6s produced instantaneous hammer, Δp=1.5 exceeding 1.0 and cracking; slow closure avoids the instantaneous hammer;
2) Use a slow-closing valve with staged closure: a single fast closure causes damage, so staging is used;
3) Check the instantaneous/indirect water-hammer criterion: the ratio of T to 2L/c determines the type, so the type is identified;
4) Install a surge arrester to cut the peak, because the amplitude exceeds the limit; hence peak absorption;
5) Raise the pipe pressure rating or wall thickness: the allowable was low, so the rating is raised;
6) Limit the closure rate in the valve program: a high rate causes hammer, so the rate is limited;
7) Periodically replay the closure curve: drift makes it close faster, so the curve is re-checked;
8) Write closure time into the procedure: the original fast closure was the root cause of the hammer, so procedure review enforces it.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection