E44-366 · Water Hammer and Pressure Surge · Low-pressure pipe, high-point hump · ★★★
A high-point hump caused liquid-column separation at pump shutdown, and the refill collision generated Δp=1.3MPa beyond the allowable limit, cracking the pipe.
[Mechanism] Negative pressure at the hump breaks the column and forms a cavity.
[Calculation] When the cavity refills the liquid columns collide, generating Δp=1.3.
[Design Omission] The hump was not eliminated and no air-injection valve was provided, leaving the line to suffer separation hammer.
1) Level the hump or fit an air-injection valve to prevent separation, because negative pressure at the hump broke the column and the refill Δp=1.3 exceeded the limit and cracked the pipe; hence remove the hump to prevent breakage;
2) Fit a double-acting air valve at the high point (exhaust/air-injection), because the cavity needs make-up air; hence double-acting valve;
3) Check the liquid-column separation threshold, because low head makes separation likely; hence separation check;
4) Raise the pipe rating to resist refill collision, because overpressure cracks it; hence higher rating;
5) Close slowly on pump shutdown to prevent breakage, because a fast stop causes separation; hence slow closing;
6) Install a surge arrester to cut the refill wave, because refilling generates hammer; hence peak absorption;
7) Use water-hammer simulation to locate separation points, because hidden points are hard to spot; hence simulation;
8) Write hump treatment into the design, because the lack of hump removal was the root cause of separation; hence design control.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection