E44-367 · Water Hammer and Pressure Surge · Thin-wall stainless steel pipe, negative pressure · ★★
The water-hammer negative-pressure wave drove the internal pressure to -0.05MPa, and the thin wall (δ=2mm) locally buckled, shrinking the diameter by 8%.
[Mechanism] The wave makes the transient pressure negative, and the thin wall buckles under instability.
[Calculation] The δ=2mm wall locally shrank by 8%.
[Design Omission] No negative-pressure resistance design and no air injection were provided, so the negative wave buckled the pipe.
1) Fit an air valve to inject air and prevent negative pressure, because the negative wave drove it to -0.05 and the thin wall buckled 8%; hence make-up pressure to prevent buckling;
2) Thicken the thin-wall pipe or add ring stiffness, because δ=2 buckles easily; hence higher stiffness;
3) Check the negative-pressure stability threshold, because the thin-wall threshold is low; hence stability check;
4) Close slowly on shutdown to prevent negative waves, because a fast stop generates negative pressure; hence slow closing;
5) Install a surge arrester to cut the wave amplitude, because the amplitude is large; hence peak absorption;
6) Raise the pipe rating to resist external pressure, because negative pressure equals external pressure; hence higher rating;
7) Use water-hammer simulation to check for negative peaks, because hidden negative pressure is hard to spot; hence simulation;
8) Write negative-pressure resistance into the design, because the lack of it was the root cause of buckling; hence design control.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection