E44-368 · Water Hammer and Pressure Surge · Flange joint, shutdown hammer · ★★
The shutdown water hammer Δp=1.1MPa blew out the flange gasket, spraying on site, and the unit had to be stopped to replace it.
[Mechanism] The hammer drove Δp beyond the flange rating and blew the gasket out.
[Calculation] The blown-out gasket caused a spraying leak.
[Design Omission] No hammer protection and no higher flange rating were provided, so the hammer caused the leak.
1) Install an arrester / slow closure to cut the hammer so that Δp≤the flange rating, because the 1.1 hammer blew the gasket and forced a shutdown; hence cut the hammer to protect the gasket;
2) Raise the flange pressure class with a margin, because a low rating was blown out; hence higher class;
3) Change to a spiral-wound metal gasket that resists impulse, because soft gaskets blow out; hence rigid gasket;
4) Tighten the bolts evenly to torque, because looseness causes leaks; hence even tightening;
5) Close first and then stop the pump, because a direct stop generates hammer; hence close first;
6) Provide a leak alarm for early detection, because leaks force shutdown; hence alarm;
7) Check the peak by water-hammer simulation, because estimates fall short; hence simulation;
8) Write flange protection into the design, because the lack of protection was the root cause of the leak; hence design control.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection