E44-369 · Water Hammer and Pressure Surge · Branch pipe DN50 thin wall · ★★
The main hammer wave transmitted into the branch drove Δp=1.4MPa beyond the branch rating of 1.0, bursting the branch and flooding the area.
[Mechanism] The main wave entering the branch overstresses the branch beyond its rating.
[Calculation] Δp=1.4 exceeded 1.0 and caused bursting.
[Design Omission] The branch was neither up-rated nor provided with relief, so it burst.
1) Raise the branch rating to ≥1.6MPa or fit a relief valve, because the main wave drove Δp=1.4 beyond 1.0 and caused bursting; hence higher rating / relief;
2) Install a water-hammer arrester at the branch takeoff, because the wave enters directly; hence branch absorption;
3) Check the branch wave-pressure distribution, because of hidden peaks; hence distribution calculation;
4) Cut the peak in the main system to reduce transmission, because the source wave is large; hence cut the source;
5) Remove weak thin-wall sections from the branch, because thin walls burst easily; hence replace with thicker wall;
6) Provide a branch overpressure interlock, because overpressure is risky; hence interlock;
7) Recheck by water-hammer simulation, because estimates fall short; hence simulation;
8) Write branch protection into the design, because the lack of up-rating was the root cause of bursting; hence design control.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection