E44-371 · Water Hammer and Pressure Surge · Low sump, backflow · ★★
After shutdown, water from the high point flowed back, reversing the pump; restarting generated hammer Δp=1.0MPa beyond the allowable limit and leaked at the shaft seal.
[Mechanism] A low-level suction lets high-point water flow back and reverse the pump.
[Calculation] Restarting stacks on the backflow to generate Δp=1.0.
[Design Omission] No check valve to prevent backflow and no slow closure were provided, so backflow caused hammer.
1) Fit a fast-closing check at the pump outlet to prevent backflow, because backflow reversed the pump, restarting drove Δp=1.0 beyond the limit and leaked at the shaft seal; hence stop backflow;
2) Close slowly to avoid restart stacking, because stacking makes it large; hence slow closing;
3) Check backflow + start Δp≤allowable, because stacking exceeds the limit; hence stacked calculation;
4) Install a surge arrester to cut the peak, because the amplitude exceeds the limit; hence peak absorption;
5) Up-rate the pump shaft seal against reverse-rotation leakage, because reverse rotation damages the seal; hence upgraded seal;
6) Close first and then stop the pump, because a direct stop lets backflow; hence close first;
7) Recheck by water-hammer simulation, because estimates fall short; hence simulation;
8) Write backflow prevention into the design, because the lack of a check was the root cause of backflow; hence design control.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection