E44-373 · Water Hammer and Pressure Surge · Control valve, oscillating closure · ★★
Control-valve oscillation made the flow pulsate, generating repeated water hammer Δp=0.8MPa, pipe vibration and 105dB noise.
[Mechanism] Valve oscillation makes the flow pulsate, and waves form repeatedly.
[Calculation] Δp=0.8 caused vibration and noise.
[Design Omission] The valve was not stabilized and no damping was provided, so oscillation hammer occurred.
1) Add a valve positioner to stabilize the opening and provide damping, because oscillation made the flow pulsate, repeatedly generating Δp=0.8 and 105 noise; hence stabilize the valve to kill pulsation;
2) Check valve stability to avoid self-excitation, because self-excitation generates vibration; hence stability check;
3) Provide a surge tank to smooth pulsation, because pulsation accumulates into hammer; hence buffering;
4) Brace the pipe supports against vibration, because vibration transmits; hence pipe bracing;
5) Control the opening/closing speed to prevent pulsation, because fast action causes pulsation; hence speed limiting;
6) Install a surge arrester to cut the wave, because waves form repeatedly; hence peak absorption;
7) Use water-hammer simulation to find pulsation peaks, because of hidden peaks; hence simulation;
8) Write valve stabilization into the control logic, because the lack of stabilization was the root cause of oscillation; hence control discipline.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection