E44-374 · Water Hammer and Pressure Surge · Check valve disc stuck open · ★★
A check valve disc stuck open let backflow on pump shutdown, and the reclosure collision generated Δp=1.2MPa beyond the allowable limit, cracking the valve body.
[Mechanism] A stuck disc keeps the backflow path open, and reclosure causes a collision.
[Calculation] Δp=1.2 exceeded the allowable limit and cracked the body.
[Design Omission] The disc was not kept free and was not serviced, so it stuck open and caused hammer.
1) Repair the check disc to keep it free and seating, because the stuck-open disc let backflow and reclosure drove Δp=1.2 beyond the limit and cracked it; hence keep the disc free to stop backflow;
2) Periodically test seating to check for sticking, because sticking develops gradually; hence seating test;
3) Provide a backup twin check valve, because a single failure is risky; hence dual protection;
4) Close slowly to avoid reclosure collision, because the collision generates hammer; hence slow closing;
5) Check backflow + closure Δp≤allowable, because stacking exceeds the limit; hence stacked calculation;
6) Up-rate the valve body to prevent cracking, because overpressure cracks it; hence higher rating;
7) Recheck by water-hammer simulation, because estimates fall short; hence simulation;
8) Put disc maintenance into the procedures, because the sticking was the root cause of the open disc; hence procedural control.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection