E44-375 · Water Hammer and Pressure Surge · Two pump stations in series · ★★★
When the upstream station tripped, downstream backflow stacked on it; the series section Δp=1.6MPa exceeded the allowable limit and the tie pipe burst.
[Mechanism] An upstream trip lets downstream backflow, and waves stack through the series.
[Calculation] Δp=1.6 exceeded the allowable limit and caused bursting.
[Design Omission] No interlocked shutdown and no staged protection were provided, so the series suffered hammer.
1) Interlock the stations to shut down downstream first and upstream later to avoid stacking, because the upstream trip let backflow stack, Δp=1.6 exceeded the limit and caused bursting; hence interlock to avoid stacking;
2) Up-rate the tie pipe to ≥2.0, because the allowable is low; hence higher rating;
3) Provide staged arresters at each station, because waves are strong through the series; hence staging;
4) Check the series-stacked Δp distribution, because of hidden peaks; hence distribution calculation;
5) Provide an overpressure interlock trip, because overpressure is risky; hence interlock;
6) Provide slow-closing checks to prevent backflow, because backflow stacks; hence slow closing;
7) Recheck by water-hammer simulation, because estimates fall short; hence simulation;
8) Write series protection into the design, because the lack of interlocking was the root cause of stacking; hence design control.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection