E44-389 · Water Hammer and Pressure Surge · Elevated-Tank Inlet Hammer · ★★
The float valve closes abruptly, producing an inlet Δp=0.9MPa that exceeds the pipe rating of 0.6 and leaks the tank-connection gasket.
[Abrupt Closure] The float valve closes and cuts the flow, generating a wave Δp=0.9.
[Leak] At 0.6 over the allowable limit, the gasket leaked.
[Design Omission] No slow-closing float valve and no arrester were provided — inlet hammer resulted.
1) Convert the float valve to a slow-closing type to control closure rate: abrupt closure made Δp=0.9 exceeding 0.6 and leaking; slow closing lowers the wave;
2) Install an arrester on the inlet pipe to cut the peak: the wave amplitude exceeds the limit, so it absorbs the peak;
3) Check inlet Δp ≤ pipe allowable: the original lack of calculation caused leakage, so accurate calculation is used;
4) Up-rate the connection or use a metal gasket: a low allowable caused leakage, so the rating is raised;
5) Limit inlet flow velocity to prevent push: high velocity generates waves, so velocity is limited;
6) Provide level-controlled slow closure: a full tank triggers abrupt closure, so slow level control is used;
7) Recheck by water-hammer simulation, because estimates fall short; hence simulation;
8) Write inlet protection into the design: the original abrupt closure was the root cause, so design review enforces it.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection