E44-391 · Water Hammer and Pressure Surge · Reciprocating Pump Pulsating Flow · ★★
Reciprocating-pump pulsation produces a pressure wave Δp=0.7MPa, pipe vibration, check-valve noise, and loosened, leaking gaskets.
[Pulsation] Reciprocating action makes the flow pulsate, generating a pressure wave Δp=0.7.
[Leakage] Vibration loosens gaskets and causes leakage.
[Design Omission] No surge chamber and no flow stabilization were provided — pulsation hammer resulted.
1) Install an air chamber at the pump discharge to smooth the pulsation: pulsation made Δp=0.7, vibration and leakage; the chamber buffers and stabilizes flow;
2) Check pulsation Δp and up-rate the rating: exceeding it loosened and leaked, so the rating is raised;
3) Anchor the pipe with fixed supports against pulsation vibration: vibration loosens gaskets, so supports are anchored;
4) Install pulsation dampers: pulsation energy is high, so damping is used;
5) Limit speed to lower the pulsation amplitude: fast cycling gives large pulsation, so speed is limited;
6) Inspect check valves for sticking to prevent impacts: sticking causes sudden events, so valves are inspected;
7) Recheck by water-hammer simulation, because estimates fall short; hence simulation;
8) Write buffering into the design: the original lack of buffering was the root cause of pulsation, so design review enforces it.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection