E44-397 · Water Hammer and Pressure Surge · Gravity Line Valve Closure · ★★
Closing a valve in a gravity line abruptly stops the water column; Δp=ρcΔv=0.9MPa exceeds the pipe rating of 0.6, and the elbow gasket leaked.
[Abrupt Stop] Closing the valve stops the water column dead; the wave reaches Δp=0.9.
[Leak] At 0.6 over the allowable limit, the gasket leaked.
[Design Omission] No slow closure and no relief — gravity-flow hammer.
1) Use slow-closing operation for gravity-line shutdown to limit the rate; an abrupt stop drove Δp to 0.9 over the 0.6 limit and caused a leak, so close slowly to cut the wave;
2) Install a relief valve to cap the peak; the wave amplitude exceeded the limit, so vent the pressure;
3) Check the shutdown Δp against the pipe rating; the leak came from an uncalculated load, so calculate it accurately;
4) Upgrade the elbow rating for leakage resistance; over-limit pressure caused the leak, so raise the rating;
5) Add a surge arrester to cut the peak; the amplitude was high, so absorb the peak;
6) Set a fixed closing speed in the shutdown procedure; fast closure causes hammer, so fix the speed;
7) Recheck by water-hammer simulation, because estimates fall short; hence simulation;
8) Write slow closure into the operating procedure; fast closure was the root cause, so lock it in at procedure level.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection