E44-1040 · Water Hammer and Pressure Surge · Quick-Closing Valve · ★★
Hammer, vibration, and noise from quick shutdown.
[Mechanism] The emergency quick-closing valve cut off the flow instantaneously; the momentum water column stopped dead, generating a water-hammer pressure rise.
[Calculation] DN200 quick-closing valve, closure time 0.5s, v=3.0m/s; ΔP=ρcΔv=1000×1000×3.0=3.0MPa, exceeding the pipe rating of 2.5MPa; the flange leaked.
[Design Omission] No slow closure, no cut-off water-hammer calculation, and no reduced-pressure operation.
1) Change to a slow-closing quick-shutdown valve (extend closure to 8s); abrupt closure caused the hammer, and slow closure cuts it, so reduce the hammer;
2) Check the cut-off rate to hold ΔP≤0.5MPa (was 3.0); excessive closing speed caused the hammer, and a checked rate protects, so keep the water hammer controlled;
3) Add a surge tank (1.5m³ capacity to absorb energy); the abrupt change had no buffer, and a tank absorbs it, so cut the peak;
4) Install upstream pressure reduction (lower v to 1.5m/s); high velocity caused the hammer, and slowing it eases it, so suppress the hammer;
5) Run a water-hammer test (measured peak ≤0.9MPa); the hammer had never been calculated, and the measurement confirms control, so set the peak by data;
6) Fit pressure sensors plus a recorder (monitor the peak); the hammer first shows as a pressure peak, so monitor and give early warning;
7) Control cut-off in operation as slow-then-stop (instantaneous cut is forbidden); abrupt cut causes hammer, and a controlled sequence protects, so prevent hammer in operation;
8) Write slow-closure and hammer calculation into the specification; the root cause of the quick-shutdown hammer was no slow closure and no hammer calculation, so lock it in at specification level.
GB/T 20801.3-2020 Design code for industrial metallic piping