E44-170 · Two-Phase Flow and Air Binding · Condensate Return Line · ★★
Liquid-full condensate return leaves unstable steam-water two-phase velocity; the line suffered water hammer and the steam trap vibrated to failure.
[Two-Phase] Steam and water coexist in an unstable flow regime.
[Impact] Slug flow generates water hammer.
[Design Omission] No steam-water separation and excessive velocity — impact.
1) Fit a steam-water separator in the return line to stabilize flow; coexisting steam and water run unstable and cause impact, so separate and steady the flow;
2) Control velocity to prevent slug flow (≤1m/s); high speed generates slug impact, so limit the speed;
3) Slope the line toward continuous drainage; trapped condensate creates two-phase flow, so slope for free drainage;
4) Select the steam trap for two-phase, impact-resistant service; it vibrated to failure, so choose an impact-resistant model;
5) Add water-hammer monitoring and alarm; impact has warning signs, so monitor and alarm;
6) Add pipe supports densely for vibration resistance; vibration loosened them, so densify the support spacing;
7) Test-run to verify a stable flow regime with no impact; the design requires measured verification, so confirm at handover;
8) Write steam-water separation into the return-line design; the missing separation was the root cause of impact, so design must include it.
GB/T 20801-2020 Pressure piping code