E44-448 · Two-Phase Flow and Gas Binding · Gas Noise in Level/Flow Measurement · ★★
Gas in the medium made the measurement signal noisy by ±5%, control became unstable, and product quality fluctuated.
[Gas Entrainment] Gas made the signal noisy by ±5%.
[Instability] The noise made control unstable and the product fluctuate.
[Design Omission] No upstream flow deaeration and no signal filtering; gas entrainment caused the noise.
1) Deaerate and vent upstream of the instrument and add signal filtering; gas caused ±5% noise, instability, and fluctuation, so deaeration and filtering stabilize the measurement;
2) Select gas-tolerant instruments; ordinary instruments are upset by gas, so change the type;
3) Provide a straight pipe run to stabilize flow; vortices cause noise, so a long straight run is used;
4) Control the gas fraction ≤2%; more gas means more noise, so control gas;
5) Periodically calibrate and compare; noise drifts, so calibrate;
6) Provide density compensation; gas changes density, so compensate;
7) Add a downstream surge tank; pulsation causes noise, so buffer it;
8) Write deaeration into the layout; gas entrainment was the root cause of the noise, so the layout gates it.