E44-472 · Filter Clogging and Contamination · Natural-Gas Filter DN100 · ★★
Separated liquid was never drained; at -15°C it froze and plugged, downstream pressure dropped 0.2MPa, and gas supply was interrupted
[Mechanism] The separated liquid accumulated and froze at low temperature, plugging the element.
[Calculation] Liquid level h=30mm blocks 40% of the flow area; at -15°C it freezes shut, Δp suddenly exceeds the limit, and supply is cut.
[Design Omission] No automatic liquid drain and no heat tracing, so accumulated liquid froze and plugged.
1) Add an automatic level-controlled drain valve to remove accumulated liquid; since 30mm of liquid blocked 40% of the area and froze shut at -15°C, cutting supply, draining prevents freeze-up;
2) Heat-trace and insulate the filter housing to hold temperature >0°C; since cold causes freezing, heat tracing prevents it;
3) Add a timed low-point drain; since liquid accumulates gradually, scheduled draining removes it;
4) Add a low outlet-pressure alarm; since plugging drops pressure, the alarm warns;
5) Add a gas-liquid separator upstream; since liquid loading was high, pre-separation removes it first;
6) Measure dew point to prevent liquid carryover; since carried liquid freezes, dew-point monitoring prevents it;
7) Inject methanol in the low-temperature section to suppress icing; since methanol lowers the pour point, injection prevents freezing;
8) Write draining and heat tracing into the procedure; since liquid was never drained, the root cause of freeze-up, the procedure provides the check.
GB/T 26114-2010 Filters for liquid filtration