E44-473 · Filter Clogging and Contamination · Seawater Screen Filter · ★★
Marine organisms colonize the screen surface, flux drops 40%, Δp=0.15MPa>0.05, and cooling water is interrupted
[Mechanism] Organisms such as oysters attach and occupy the screen openings.
[Calculation] Fouling shrinks the effective area 40%, v=Q/A rises 1.7x, and Δp=ξρv²/2=0.15.
[Design Omission] No chlorination, no screen flushing, and no protection, so fouling clogged the screen.
1) Chlorinate upstream to suppress fouling; since fouling shrank the area 40%, v rose 1.7x, and Δp=0.15, suppressing fouling keeps flow open;
2) Install a rotary brush for automatic screen cleaning; since fouling builds gradually, brushing removes it;
3) Coat the screen with anti-fouling paint; since the plain screen fouled easily, coating prevents it;
4) Flush periodically with high-pressure water; since fouling hardens on, water jetting removes it;
5) Set a Δp alarm at 0.05; since exceeding it drops flow, the alarm warns;
6) Upgrade the screen to corrosion-resistant stainless steel; since seawater causes corrosion, stainless steel resists it;
7) Keep a spare screen for rotation; since cleaning interrupts service, rotation avoids shutdown;
8) Write fouling suppression and screen cleaning into the seawater piping procedure; since fouling was never suppressed, the root cause, the seawater procedure provides the check.
GB/T 26114-2010 Filters for liquid filtration