E44-488 · Filter Blockage and Fouling · Steam Filter DN50 · ★★
Trap blocked, water logging, start-stop water hammer, filter housing cracked by vibration, wet steam
[Mechanism] Poor drainage lets condensate accumulate, causing steam-water mixed hammer.
[Calculation] The water head h causes an abrupt steam-velocity change; the water-hammer pressure Δp=ρcΔv=2MPa exceeds the housing rating and cracks it.
[Design Omission] No steam trap fitted and no condensate drained; water hammer results.
1) Install a steam trap and regularly drain condensate, because the original water logging, Δp=2MPa and cracking caused the failure, so drainage prevents hammer;
2) Drain condensate before admitting steam on startup, because wet steam causes hammer, so drain first;
3) Add bracing to the filter housing to prevent vibration cracking, because vibration cracked it, so bracing is added;
4) Set a water-hammer alarm, because hammer damages the housing, so an alarm is provided;
5) Size the trap piping adequately, because a small bore blocks, so adequate bore is used;
6) Monitor steam dryness, because wet steam hammers, so dryness is monitored;
7) Inspect the steam trap regularly, because blockage grows gradually, so the trap is inspected;
8) Write trapping and condensate drainage into the steam-filter specification, because the lack of trapping was the root cause of hammer, so the steam-filter spec governs.
GB/T 26114-2010 Liquid filters - Filters for filtration