E44-1057 · Filter Blockage and Fouling · Filter Cartridge · ★★
Differential pressure not monitored, blocked, pressure drop
[Mechanism] The cartridge clogs with no differential-pressure monitoring; it is found only at the limit, by which time downstream flow has already dropped sharply.
[Calculation] Cartridge 80% blocked, ΔP=0.35MPa (no alarm set), flow down 45%, only then stopped for inspection.
[Design Omission] No differential-pressure monitoring, alarm value not checked, no scheduled inspection.
1) Install a differential-pressure transmitter (real-time ΔP monitoring), because no monitoring let it block and monitoring gives early notice, so warning is provided;
2) Set the alarm value (alarm at ΔP>0.15MPa), because high differential pressure means blockage and the alarm value triggers it, so cleaning is timely;
3) Add a bypass (maintains flow on blockage), because blockage cuts flow and the bypass protects it, so flow continues;
4) Increase cartridge capacity (larger chamber), because small capacity causes blockage and added capacity eases it, so resistance to blockage improves;
5) Run a monitoring test (ΔP correlated with blockage rate), because blockage was not checked and measurement confirms the relation, so monitoring is set by data;
6) Install remote indication (visible in the control room), because blockage first shows as differential pressure and early notice helps, so blockage is monitored and warned;
7) Control the cleaning interval in operation (clean by ΔP), because long operation causes blockage and controlled timing cleans it, so operational blockage prevention is applied;
8) Write pressure monitoring and alarm setting into the specification, because the root cause of unmonitored differential pressure was omitted monitoring and an unchecked alarm value, so the specification governs.
HG/T 21637-1991 Chemical-industry piping filters