Knowledge Base › Fluid Systems Error Case › Cooler Water-Side Fouling Drops Heat-Transfer Coefficient and Overheats Equipment

Cooler Water-Side Fouling Drops Heat-Transfer Coefficient and Overheats Equipment

E44-022 · Heat-Exchanger Fouling and Insufficient Heat Transfer · Plate Heat Exchanger · ★★

Problem Description

A 1.2mm thick water scale cuts the overall heat-transfer coefficient by 40%, outlet oil temperature rises by 8℃, and equipment overheats.

Root Cause

[Fouling Resistance] The scale-layer thermal resistance R=δ/λ=0.0012/1.5=8e-4, accounting for 50% of total thermal resistance.
[Temperature Rise] The drop in K leaves Q=KAΔTm insufficient, and the oil temperature exceeds design by 8℃.
[Design Omission] No water treatment was provided and no periodic cleaning was scheduled; fouling caused the heat transfer to drop.

Corrective Solution

1) Dose and soften the circulating water to control hardness, since high hardness is the fouling source and the fouling resistance R=δ/λ accounts for 50% of thermal resistance, thus controlling hardness to reduce scale;
2) Provide online cleaning (sponge balls / brushes) to remove scale, since continuous online cleaning prevents scale buildup and keeps K from dropping 40%, thus preserving heat transfer;
3) Periodically chemically clean to restore K, since chemical scale dissolution returns K to design, thus restoring it on a cycle;
4) Control the flow velocity at ≥1m/s to prevent deposition, since low velocity lets particles settle and form scale, thus raising velocity to suppress settling;
5) Fit inlet filtration and side-stream filtration, since removing suspended solids reduces wall adhesion and thus cuts the fouling source;
6) Monitor terminal temperature difference and inlet/outlet temperature difference, since a rising terminal difference and oil 8℃ over design are fouling signals, thus giving trend warning;
7) Measure the heat-transfer coefficient to design value on test run, since restored K means sufficient heat transfer, thus accepting the unit;
8) Bring water-quality management into heat-exchanger operation, since the original lack of water treatment was the root cause of fouling, so it must be managed in service.

Checklist

Reference

GB/T 151-2014 Heat exchangers

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »