Condenser Copper-Tube Fouling Drops Vacuum and Raises Terminal Difference

E44-023 · Heat-Exchanger Fouling and Insufficient Heat Transfer · Condenser · ★★

Problem Description

Copper-tube fouling drops vacuum by 4kPa, raises coal consumption, and raises the terminal difference by 6℃.

Root Cause

[Terminal Difference] Fouling raises the terminal difference Δt and reduces utilization of the heat-transfer temperature drop.
[Vacuum] Rising condensation temperature raises exhaust pressure and lowers unit efficiency.
[Design Omission] No sponge-ball cleaning was fitted and no chemical was dosed into the circulating water; fouling caused the vacuum to drop.

Corrective Solution

1) Provide a continuous sponge-ball cleaning system, since balls scrub the tubes so scale does not adhere and the terminal difference does not rise, thus preserving vacuum;
2) Dose the circulating water with antiscalant and corrosion inhibitor, since the chemicals suppress scale deposition and corrosion, thus reducing fouling;
3) Periodically clean tubes with high-pressure water jetting, since the jet removes hard scale and restores K, thus cleaning on a cycle;
4) Control the concentration ratio to prevent scale deposition, since an excessively high ratio causes salt precipitation and scaling, thus controlling the ratio;
5) Monitor terminal difference and vacuum trends, since a 4kPa vacuum drop and 6℃ terminal-difference rise are fouling signals, thus giving warning;
6) Provide secondary inlet filtration to reduce fouling, since removing suspended solids reduces wall adhesion, thus lowering contamination;
7) Measure tube scale thickness and K during maintenance, since quantifying scale thickness guides cleaning, thus maintaining by data;
8) Bring cleaning into condenser maintenance, since the original absence of sponge-ball cleaning was the root cause of vacuum loss, so maintenance must include it.

Checklist

Reference

GB/T 7119-2018 Chemical industry water-conservation standard